DFW-0.4 LV Cable Branch Box
Companion box for urban cable conversion: taps, branches, relays or switches LV cables among box substations, switch cabinets and ring units — stainless build with rain-, corrosion- and insect-proof ventilated design, −50…+60 °C.
- Floor-, wall- or pole-mounted variants cover most sites; indoor and outdoor types available
- Body precision-fabricated and welded from cold-rolled or stainless steel — “three-proof + ventilation”: rain/s
- Complete primary schemes: knife switches, switch-fuses or breakers freely chosen as in/out elements
A cleaner, more reliable approach to MV switching
The HP-ELS series replaces SF₆ with environmentally friendly insulating media while keeping the proven safety and performance utilities expect from gas-insulated switchgear.
Product Overview
The DFW-0.4 low-voltage cable branch box is supporting equipment for urban-grid cabling upgrades. Installable outdoors, indoors or underground, it connects power cables with box-type transformers, load-switch cabinets, load-fuse combination cabinets and ring-main supply units, serving as tapping, branching, relaying or switching to greatly facilitate cable networking.
Technical specifications
Headline ratings at a glance, followed by the full technical data sheet. Exact values are confirmed per project configuration.
| Parameter | Value |
|---|---|
| Rated voltage / current | 0.4 kV / 100 A |
| Short-time / peak withstand | 20 kA·3s / 50 kA |
| DC withstand 15 min / PF 5 min | 52 kV / 45 kV |
| Lightning impulse withstand | 105 kV |
| Partial discharge / loop resistance | ≤10 pC/15kV · ≤4 μΩ |
| Protection / ambient | IP33 · −50~+60 ℃ |
| Applicable cable section | 25 – 400 mm² |