Gas-Insulated RMU

HP-SRM SF6 Gas-Insulated Ring Main Unit

Modular SF6 RMU for 12/24/40.5 kV: C/F/V/SV/SL/M/PT units freely combined in a sealed IP67 gas tank, with left/right extension and flexible cable entry.

Factory-direct supply Worldwide delivery & export documentation 12-month warranty · extended options
  • Rated voltage: 12 / 24 / 40.5 kV
  • Cabinet type: C load switch · F fuse combination · V vacuum breaker · SV/SL bus sectioning · M metering · PT c
  • Rated current: 630 A or 1250 A
  • Extension: I left · D right · ID both sides · blank non-extendable
  • Cable entry: L left · R right · LR both sides
  • Example: HP-SRM-12-V-12/630DL — load-switch cabinet, 12 kV, 630 A, right extension, left cable entry
Overview

A cleaner, more reliable approach to MV switching

The HP-ELS series replaces SF₆ with environmentally friendly insulating media while keeping the proven safety and performance utilities expect from gas-insulated switchgear.

Product Overview

The HP-SRM-12/24/40.5 series SF₆ gas-insulated ring main unit uses SF₆ gas as the insulating and arc-extinguishing medium in a fully sealed gas-tank structure (SF₆ rated pressure 14 bar, annual leakage ≤ 0.05 %/year). It is flexibly composed of load-switch (C), load-switch-fuse (F), vacuum-breaker (V) and isolator/earthing-switch units, with extension and two-side cable in/out options, rated 12 / 24 / 40.5 kV. The SF₆ gas compartment reaches IP67 and the enclosure IP4X; it is maintenance-free and reliable, suited to power reception and distribution in three-phase AC ring networks and terminal distribution systems.

Specifications

Technical specifications

Headline ratings at a glance, followed by the full technical data sheet. Exact values are confirmed per project configuration.

Rated voltage12 / 24 / 40.5kV
Rated current (busbar)630 / 1250A
Power-frequency withstand (earth & ph / break)42 / 48kV
Lightning impulse withstand (earth & ph / break)75 / 85kV
ParameterValue
Rated voltage12 / 24 / 40.5 kV
Rated current (busbar)630 / 1250 A
Power-frequency withstand (earth & ph / break)42 / 48 kV
Lightning impulse withstand (earth & ph / break)75 / 85 kV
Rated short-circuit breaking current (V module)20 / 25 / 31.5 kA
Rated short-circuit making current (peak)50 / 63 kA
Short-time withstand current / duration20 · 25 kA / 4 s
Mechanical life5000 ops
SF6 gas compartment / fuse tubeIP67
Switchgear enclosureIP4X
Main busbar / earthing busbar240 / 160 mm² Cu
Model Meaning

Reading the model designation

HP-SRM Product model
12 Rated voltage (12/24/40.5) kV
Cabinet type: C Load / F Fuse-comb. / V VCB / SV·SL Bus-section / M Metering / PT PT
Rated current (630/1250) A
Extension: I left / D right / ID both / blank none
Cable in/out: L left / R right / LR both / blank none

Generated automatically from each product's model code.

Need help selecting for your project?

Send us your single-line diagram or requirements — our engineers will provide configuration, full specifications and export documentation.

Request a quote
Factory-direct supply Worldwide delivery Export documentation