HP-SIS-12 Solid-Insulated Ring Main Unit

Fully insulated, fully enclosed, maintenance-free vacuum RMU — epoxy-cast live parts and solid insulated busbars, ideal for harsh environments from high altitude to heavy pollution.

Factory-direct supply Worldwide delivery & export documentation 12-month warranty · extended options
  • Rated voltage (kV) · rated current (A) · switch type (C load switch / V breaker / G disconnector / F load-swit
Overview

A cleaner, more reliable approach to MV switching

The HP-ELS series replaces SF₆ with environmentally friendly insulating media while keeping the proven safety and performance utilities expect from gas-insulated switchgear.

Product Overview

The HP-SIS-12 series is a fully-insulated, fully-enclosed, maintenance-free solid-insulated vacuum switchgear. All high-voltage live parts are cast in epoxy resin of excellent insulation performance, integrating the vacuum interrupter, main conductive circuit and insulating supports into one body; functional units are joined by fully-insulated solid busbars, so the whole assembly is immune to the external environment, ensuring reliability and operator safety.

Applications

With a simple structure, flexible operation, reliable interlocking and easy installation, it suits 50 Hz, 12 kV systems and is widely used in industrial and civil cable ring networks and distribution terminals for power reception and distribution. It is especially suited to urban residential distribution, small substations, switching stations, cable branch boxes, box-type substations, industrial sites, malls, airports, subways, wind farms, hospitals, stadiums, railways and tunnels; its full insulation, sealing and shielding make it ideal for harsh environments such as high altitude, high temperature, damp heat, severe cold and heavy pollution.

Specifications

Technical specifications

Headline ratings at a glance, followed by the full technical data sheet. Exact values are confirmed per project configuration.

Rated voltage / frequency12 kV / 50 Hz
Rated current630 / 1250A
PF withstand (break / ph-ph / ph-E)48 / 42 / 42kV
Impulse withstand (break / ph-ph / ph-E)85 / 75 / 75kV
ParameterValue
Rated voltage / frequency12 kV / 50 Hz
Rated current630 / 1250 A
PF withstand (break / ph-ph / ph-E)48 / 42 / 42 kV
Impulse withstand (break / ph-ph / ph-E)85 / 75 / 75 kV
Rated short-circuit breaking current25 / 31.5 kA
Rated short-time withstand current25 / 31.5 kA
Peak withstand / making current63 / 80 kA
Protection degree / operationIP4X · spring-charged
Load-switch PT cabinet (CPT)500×950×1650
Breaker cabinet (V / VB / VZ)400×950×1650
Bus riser cabinet (G)400×950×1650
Load-switch fuse cabinet (F)500×950×1650
Model Meaning

Reading the model designation

HP-SIS Product model
12 Rated voltage kV
630 Rated current A
Switch type: C Load / V Breaker / G Disconnector / F Load-Fuse
B: w/o earthing switch / Z: lower vertical outlet
Rated short-time withstand current kA

Generated automatically from each product's model code.

Dimensions

Overall dimensions

Cabinet height, width and depth options. Selection depends on cable type and incoming / outgoing configuration.

ItemDimensions (mm)Scope of application
Width W400 / 500Standard / CPT·F cabinet
Depth D950All models
Height H1650All models